NCDOL Header
Home About NCDOL Contact Us Calendar Publications Statistics What's New Site Map Search our Site


Boiler Safety Bureau

arrow Air Tanks Do Explode (PDF)
arrow Submit an Inspection
    Request
arrow Annual Report
arrow Boiler Safety Newsletter
arrow Application for Commission
    as an Inspector of Boilers
    Pressure Vessels
arrow Boiler Safety Laws &
    Regulations
arrow Boiler Inspectors
arrow FAQ's
arrow Policy Notices
arrow 2008 Survey Results
arrow Related Links
arrow Strategic Plan
arrow Inspection Report for     Inspectors Only PDFWord
arrow File Disclosure Requests


Bureau Contacts

Alerts Updated


Standars & Inspections

Apprenticeship & Training
Boiler Safety
Elevator & Amusement Device
Employment Discrimination
Mine & Quarry
Wage & Hour


To Power Boilers Owners/Operators and Equipment Suppliers
Brass Ball Valve Failure in Power Boiler Service

A threaded NPS 2 forging brass ball valve, with a marked steam working pressure of 150 psig, failed while in service as a high pressure steam boiler blow-off valve. The boiler was designed to operate at a maximum allowable pressure of 125 psi. The failure occurred when the body of the valve, which was of two-piece construction, came apart, resulting in the release of high temperature water and steam from the boiler. In this incident, a worker in the vicinity of the boiler received serious burns and later died in hospital.

While the cause of the incident might not be the material specification, the preliminary findings of an Alberta Boilers Safety Association investigation into the incident indicate the forging brass material specification of the valve was not permissible for a boiler external piping application.

Boiler blow-off valves and the piping that joins the valves and other fittings to the boiler must be designed and constructed in compliance with the requirements of the ASME B31.1 Power Piping Code for boiler external piping. The material specification of the valve body design was identified as ASTM B283 C37700, forging brass. While this material is permitted by ASME B31.1 for use in some applications, its use in boiler external piping is specifically prohibited (see Note 1 of Table A-6, ASME B31.1).

All power boiler owners and equipment suppliers are asked to review the material specifications of valves and other fittings used in power boiler service and to replace immediately any inappropriate ones when they are found.

It is important to note that markings on valves and other fittings may not provide complete information to allow a user to determine whether or not these fittings are suitable for a given application, such as boiler external piping. Also, material identification may not be on a fitting or in the manufacturer's sales brochure of the fitting. It is the user's responsibility to ensure that any fitting he or she is using is suitable for the intended purpose and complies with the applicable Code adopted under the Uniform Boiler and Pressure Vessel Act and the N.C. Administrative Code, Title 13, Chapter 13. Where full information is not immediately available, the user should contact the supplier or the manufacturer to get the necessary details.

 

Base information of incident provided by courtesy of:
K. T. Lau, Ph.D., P.E.
Chief Inspector and Administrator
Pressure Equipment
ASBA
Province of Alberta, CA

 

 